Interactive ISO 7730 & ASHRAE 55 evaluation comparing All-Air VAV against Hydronic Radiant + DOAS
Coupled cooling & dehumidification on a single 6°C coil. Requires cold supply air and higher air speeds, creating draft discomfort.
Cooled ceiling/floor surfaces absorb sensible heat silently at 15–16°C water temp while dry DOAS air controls humidity without drafts.
Retrofit solution where radiant panels cannot be installed. Passive heat pipes pre-cool incoming air and reheat supply air for free.
| Thermodynamic & Comfort Parameter | Calculated Value | Engineering Benchmark / Status |
|---|---|---|
| Moist Air Specific Enthalpy (h) | 49.8 kJ/kg | Total thermal energy of indoor air |
| Wet-Bulb Temperature (Twb) | 17.8 °C | Adiabatic saturation temperature |
| Local Draft Risk Rate (DR) | 4.2 % | Draft-Free (< 10% ISO Category A) |
| Recommended Chilled Water Supply (CHWS) | 16.0 °C | High-Temp Radiant Mode (+28% Chiller COP) |