DIMS Engineering Suite Thermal Comfort & Psychrometrics

Thermal Comfort, Microclimate & Psychrometric Simulator

Interactive ISO 7730 & ASHRAE 55 evaluation comparing All-Air VAV against Hydronic Radiant + DOAS

ISO 7730 (PMV / PPD) ASHRAE 55 Decoupled Latent Control
Comparative System Scenarios (Select to Benchmark) Click any system to load its operating microclimate

1. Conventional All-Air VAV System

Active

Coupled cooling & dehumidification on a single 6°C coil. Requires cold supply air and higher air speeds, creating draft discomfort.

Ta: 22.0°C Tr: 24.5°C RH: 62% Draft Risk: High

2. Hydronic Radiant + Dedicated DOAS

Active

Cooled ceiling/floor surfaces absorb sensible heat silently at 15–16°C water temp while dry DOAS air controls humidity without drafts.

Ta: 24.8°C Tr: 22.0°C RH: 50% ISO Cat. A Comfort

3. All-Air with Wrap-Around Heat Pipes

Active

Retrofit solution where radiant panels cannot be installed. Passive heat pipes pre-cool incoming air and reheat supply air for free.

Ta: 23.5°C Tr: 24.0°C RH: 48% Zero Electric Reheat
Operative Temp (Top)
23.4°C
Optimal Comfort Zone
Predicted Mean Vote
-0.09
ISO 7730 Category A
Dissatisfied (PPD)
5.2%
PPD < 6% (Ideal)
Indoor Dew Point
13.7°C
Safe Margin (>2.0 K)
Humidity Ratio (W)
9.8 g/kg
ASHRAE 55 Compliant
Chiller COP Lift
+28% COP
16.0°C High-Temp CHWS
Microclimate Control Variables Live Sliders
Dry-Bulb Air Temperature (Ta) 24.8 °C
Ambient air temperature measured by wall sensor
Mean Radiant Temperature (Tr) 22.0 °C
Weighted surface temperature (cooled ceiling/floor vs facade)
Relative Humidity (RH) 50 %
Controlled via dedicated DOAS dehumidification
Local Air Velocity (Va) 0.08 m/s
Radiant operates silently (<0.10 m/s); VAV diffusers >0.22 m/s
Clothing Insulation (Icl) 0.65 clo
Metabolic Activity (Met) 1.10 met
ASHRAE 55 / ISO 7730 Psychrometric Comfort Chart Click or drag on chart to test air states
Thermodynamic & Comfort Parameter Calculated Value Engineering Benchmark / Status
Moist Air Specific Enthalpy (h) 49.8 kJ/kg Total thermal energy of indoor air
Wet-Bulb Temperature (Twb) 17.8 °C Adiabatic saturation temperature
Local Draft Risk Rate (DR) 4.2 % Draft-Free (< 10% ISO Category A)
Recommended Chilled Water Supply (CHWS) 16.0 °C High-Temp Radiant Mode (+28% Chiller COP)
Radiant Advantage: At 24.8°C air temp and 22.0°C radiant surface temp, occupants experience a comfortable 23.4°C Operative Temperature with zero cold drafts and 28% higher chiller efficiency.